Please
Do Not Use This Reference Material WORD FOR WORD View Terms Of usage policy Page of this site for more Info on how to
use this site
Title: The transformer
Aim: To perform the
open-circuit test, short-circuit test and load test in order to;
1. Determine its equivalent circuit parameters
2. Predict
its performance characteristics on load
3.
Compare predicted results with actual performance results
Apparatus: See your laboratory manual for the apparatus.
Please
Do Not Use This Reference Material WORD FOR WORD View Terms Of usage policy Page of this site for more Info on how to
use this site
THEORY:
Open Circuit and Short Circuit Tests on Single
Phase Transformer
The efficiency and
regulation of a transformer on any load condition and at any power factor
condition can be predetermined by indirect loading method. In this method, the actual
load is not used on transformer. But the equivalent circuit parameters of a
transformer are determined by conducting two tests on a transformer which are,
1.
Open circuit test (O.C Test)
2. Short circuit test (S.C.Test)
2. Short circuit test (S.C.Test)
The parameters calculated from these test
results are effective in determining the regulation and efficiency of a
transformer at any load and power factor condition, without actually loading
the transformer. The advantage of this method is that without much power loss the
tests can be performed and results can be obtained. Let us discuss in detail
how to perform these tests and how to use the results to calculate equivalent
circuit parameters.
1. Open Circuit Test (O.C. Test)
The experimental circuit to conduct O.C test is shown in the Fig. 1.
The transformer
primary is connected to a.c. supply through ammeter, wattmeter and variac. The
secondary of transformer is kept open. Usually low voltage side is used as
primary and high voltage side as secondary to conduct O.C test.
The primary is
excited by rated voltage, which is adjusted precisely with the help of a
variac. The wattmeter measures input power. The ammeter measures input current.
The voltemeter gives the value of rated primary voltage applied at rated
frequency.
Sometimes a
voltmeter may be connected across secondary to measure secondary voltage which
is V2 = E2 when primary is supplied with rated voltage.
As voltmeter resistance is very high, though voltmeter is connected, secondary
is treated to be open circuit as voltmeter current is always negligibly small.
When the primary voltage
is adjusted to its rated value with the help of variac, readings of ammeter and
wattmeter are to be recorded.
The
observation table is as follows
Vo = Rated voltage
Wo = Input power
Io = Input current = no load current
As transformer
secondary is open, it is on no load. So current drawn by the primary is no load
current Io. The two components of this no load current are,
Im = Io sin Φo
Ic = Io cos Φo
where cos Φo = No load power factor
And hence power input can be written as,
Wo = Vo Io cos Φo
The phasor diagram is shown in the Fig. 2.
Ic = Io cos Φo
where cos Φo = No load power factor
And hence power input can be written as,
Wo = Vo Io cos Φo
The phasor diagram is shown in the Fig. 2.
As secondary is
open, I2 = 0. Thus its reflected current on primary is also zero. So
we have primary current I1 =Io. The transformer no load
current is always very small, hardly 2 to 4 % of its full load value. As I2
= 0, secondary copper losses are zero. And I1 = Io is
very low hence copper losses on primary are also very very low. Thus the total
copper losses in O.C. test are negligibly small. As against this the input
voltage is rated at rated frequency hence flux density in the core is at its
maximum value. Hence iron losses are at rated voltage. As output power is zero
and copper losses are very low, the total input power is used to supply iron
losses. This power is measured by the wattmeter i.e. Wo. Hence the
wattmeter in O.C. test gives iron losses which remain constant for all the
loads.
...
Wo
= Pi = Iron losses
Calculations : We know that,
Wo = Vo Io cos Φ
cos Φo = Wo /(Vo Io ) = no load power factor
Once cos Φo is known we can obtain,
Ic = Io cos Φo
and Im = Io sin Φo
Once Ic and Im are known we can determine exciting circuit parameters as,
Ro = Vo /Ic Ω
and Xo = Vo /Im Ω
Calculations : We know that,
Wo = Vo Io cos Φ
cos Φo = Wo /(Vo Io ) = no load power factor
Once cos Φo is known we can obtain,
Ic = Io cos Φo
and Im = Io sin Φo
Once Ic and Im are known we can determine exciting circuit parameters as,
Ro = Vo /Ic Ω
and Xo = Vo /Im Ω
Key Point : The no load power factor cos Φo
is very low hence wattmeter used must be low power factor type otherwise there
might be error in the results. If the meters are connected on secondary and
primary is kept open then from O.C. test we get Ro' and Xo'
with which we can obtain Ro and Xo knowing the
transformation ratio K.
2. Short Circuit Test (S.C. Test)
In this test, primary is connected to a.c. supply through variac, ammeter and
voltmeter as shown in the Fig. 3.
The secondary is
short circuited with the help of thick copper wire or solid link. As high
voltage side is always low current side, it is convenient to connect high
voltage side to supply and shorting the low voltage side.
As secondary is shorted,
its resistance is very very small and on rated voltage it may draw very large
current. Such large current can cause overheating and burning of the
transformer. To limit this short circuit current, primary is supplied with low
voltage which is just enough to cause rated current to flow through primary
which can be observed on an ammeter. The low voltage can be adjusted with the
help of variac. Hence this test is also called low voltage test or reduced
voltage test. The wattmeter reading as well as voltmeter, ammeter readings are
recorded. The observation table is as follows,
Now the current
flowing through the windings are rated current hence the total copper loss is
full load copper loss. Now the voltage supplied is low which is a small fraction
of the rated voltage. The iron losses are function of applied voltage. So the
iron losses in reduced voltage test are very small. Hence the wattmeter reading
is the power loss which is equal to full load copper losses as iron losses are
very low.
...
Wsc
= (Pcu) F.L. = Full load copper loss
Calculations : From S.C. test readings we can write,
Wsc = Vsc Isc cos Φsc
... cos Φsc = Vsc Isc /Wsc = short circuit power factor
Wsc = Isc2 R1e = copper loss
... R1e =Wsc /Isc2
while Z1e =Vsc /Isc = √(R1e2 + X1e2)
... X1e = √(Z1e2 - R1e2)
Calculations : From S.C. test readings we can write,
Wsc = Vsc Isc cos Φsc
... cos Φsc = Vsc Isc /Wsc = short circuit power factor
Wsc = Isc2 R1e = copper loss
... R1e =Wsc /Isc2
while Z1e =Vsc /Isc = √(R1e2 + X1e2)
... X1e = √(Z1e2 - R1e2)
Thus we get the
equivalent circuit parameters R1e, X1e and Z1e.
Knowing the transformation ratio K, the equivalent circuit parameters referred
to secondary also can be obtained.
Important Note : If the transformer is step up transformer,
its primary is L.V. while secondary is H.V. winding. In S.C. test, supply is
given to H.V. winding and L.V is shorted. In such case we connect meters on H.V.
side which is transformer secondary through for S.C. test purpose H.V side acts
as primary. In such case the parameters calculated from S.C. test readings are
referred to secondary which are R2e, Z2e and X2e.
So before doing calculations it is necessary to find out where the readings are
recorded on transformer primary or secondary and accordingly the parameters are
to be determined. In step down transformer, primary is high voltage itself to
which supply is given in S.C. test. So in such case test results give us
parameters referred to primary i.e. R1e, Z1e and X1e.
Key point : In short, if meters are connected to
primary of transformer in S.C. test, calculations give us R1e and Z1e
if meters are connected to secondary of transformer in S.C. test calculations
give us R2e and Z2e.
3. Calculation of Efficiency from O.C. and
S.C. Tests
We know that,
From O.C. test, Wo = Pi
From S.C. test, Wsc = (Pcu) F.L.
From O.C. test, Wo = Pi
From S.C. test, Wsc = (Pcu) F.L.
Thus for any p.f. cos Φ2 the efficiency can be predetermined. Similarly at any load which is fraction of full load then also efficiency can be predetermined as,
where n = fraction of full load
where
I2= n (I2) F.L.
4 Calculation of Regulation
From S.C. test we get the equivalent circuit parameters referred to primary or
secondary.
The rated voltages V1,
V2 and rated currents (I1) F.L. and (I2) F.L.
are known for the given transformer. Hence the regulation can be determined as,
where I1, I2 are rated currents for full load regulation.
For any other load the currents I1, I2 must be changed by fraction n.
... I1, I2 at any other load = n (I1) F.L., n (I2) F.L.
For any other load the currents I1, I2 must be changed by fraction n.
... I1, I2 at any other load = n (I1) F.L., n (I2) F.L.
Key Point : Thus regulation at any load and any power
factor can be predetermined, without actually loading the transformer.
For Procedure and Circuit Diagram, See your Electrical
Laboratory Manual on page 3.
Fill Up Tables in Your Manual and Continue
To….
PRECAUTIONS:
For Precautions, See General Electrical Lab Precautions
Answers to Questions:
No Questions in this
experiment.
Please
Do Not Use This Reference Material WORD FOR WORD View Terms Of usage policy Page of this site for more Info on how to
use this site
Blogger Comment
Facebook Comment