EE313 - The transformer


Please Do Not Use This Reference Material WORD FOR WORD View Terms Of usage policy Page of this site for more Info on how to use this site

Title: The transformer

Aim: To perform the open-circuit test, short-circuit test and load test in order to;
1. Determine its equivalent circuit parameters
2. Predict its performance characteristics on load
3. Compare predicted results with actual performance results

Apparatus: See your laboratory manual for the apparatus.

Please Do Not Use This Reference Material WORD FOR WORD View Terms Of usage policy Page of this site for more Info on how to use this site

THEORY:
 Open Circuit and Short Circuit Tests on Single Phase Transformer
       The efficiency and regulation of a transformer on any load condition and at any power factor condition can be predetermined by indirect loading method. In this method, the actual load is not used on transformer. But the equivalent circuit parameters of a transformer are determined by conducting two tests on a transformer which are,
1. Open circuit test (O.C Test)
2. Short circuit test (S.C.Test)
      
The parameters calculated from these test results are effective in determining the regulation and efficiency of a transformer at any load and power factor condition, without actually loading the transformer. The advantage of this method is that without much power loss the tests can be performed and results can be obtained. Let us discuss in detail how to perform these tests and how to use the results to calculate equivalent circuit parameters.

1. Open Circuit Test (O.C. Test)
       The experimental circuit to conduct O.C test is shown in the Fig. 1.

https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEgfHRPvzIkY7WavmPpJRFDC8-hsw2ba8ApmkrwlhwndbQoOqAT8xgzbWlsWr4vyXw4FUGFpzyOakVulFRMg6uAOn-bfBer5hosxMc0gpVXVzJSlZFXgEjp_E_aL9jcXsajjMy3duTa11bU/s1600/ABB1.jpeg
Fig 1. Experimental circuit for O.C. test

       The transformer primary is connected to a.c. supply through ammeter, wattmeter and variac. The secondary of transformer is kept open. Usually low voltage side is used as primary and high voltage side as secondary to conduct O.C test.
       The primary is excited by rated voltage, which is adjusted precisely with the help of a variac. The wattmeter measures input power. The ammeter measures input current. The voltemeter gives the value of rated primary voltage applied at rated frequency.
       Sometimes a voltmeter may be connected across secondary to measure secondary voltage which is V2 = E2 when primary is supplied with rated voltage. As voltmeter resistance is very high, though voltmeter is connected, secondary is treated to be open circuit as voltmeter current is always negligibly small.
      When the primary voltage is adjusted to its rated value with the help of variac, readings of ammeter and wattmeter are to be recorded.
The observation table is as follows
https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEijRlajTGzHjchXlAh_Bq2vKLS33WJAQrZOYsZV19xppa2smRdyXODQ2-tcyqGmJGVqPoOZJp9Mn_i8j3rggQaEeiXi14W3J4udzoe11NWvkoa4ixAcDJYTLAI7-qjGhzCfa4nBLUyc7lA/s1600/ABB11.jpeg

          Vo = Rated voltage
          Wo = Input power
           Io = Input current = no load current
       As transformer secondary is open, it is on no load. So current drawn by the primary is no load current Io. The two components of this no load current are,
           Im = Io sin Φo
           Ic = Io cos Φo
where  cos Φo = No load power factor
And hence power input can be written as,
           Wo = Vo Io cos Φo
       The phasor diagram is shown in the Fig. 2.

Fig. 2

       As secondary is open, I2 = 0. Thus its reflected current on primary is also zero. So we have primary current I1 =Io. The transformer no load current is always very small, hardly 2 to 4 % of its full load value. As I2 = 0, secondary copper losses are zero. And I1 = Io is very low hence copper losses on primary are also very very low. Thus the total copper losses in O.C. test are negligibly small. As against this the input voltage is rated at rated frequency hence flux density in the core is at its maximum value. Hence iron losses are at rated voltage. As output power is zero and copper losses are very low, the total input power is used to supply iron losses. This power is measured by the wattmeter i.e. Wo. Hence the wattmeter in O.C. test gives iron losses which remain constant for all the loads.
...          Wo = P= Iron losses
       Calculations : We know that,
             Wo = Vo Io cos Φ
             cos Φo = Wo /(Vo Io ) = no load power factor
Once cos Φo is known we can obtain,
              I= Io cos Φo
 and        Im = Io sin Φo
       Once Iand Im are known we can determine exciting circuit parameters as,
              Ro = Vo /Ic   Ω
and        Xo = Vo /Im  
Key Point : The no load power factor cos Φo is very low hence wattmeter used must be low power factor type otherwise there might be error in the results. If the meters are connected on secondary and primary is kept open then from O.C. test we get Ro' and Xo' with which we can obtain Ro and Xo knowing the transformation ratio K.

2. Short Circuit Test (S.C. Test)
       In this test, primary is connected to a.c. supply through variac, ammeter and voltmeter as shown in the Fig. 3.

Fig. 3 Fig 1. Experimental circuit for O.C. test

       The secondary is short circuited with the help of thick copper wire or solid link. As high voltage side is always low current side, it is convenient to connect high voltage side to supply and shorting the low voltage side.
       As secondary is shorted, its resistance is very very small and on rated voltage it may draw very large current. Such large current can cause overheating and burning of the transformer. To limit this short circuit current, primary is supplied with low voltage which is just enough to cause rated current to flow through primary which can be observed on an ammeter. The low voltage can be adjusted with the help of variac. Hence this test is also called low voltage test or reduced voltage test. The wattmeter reading as well as voltmeter, ammeter readings are recorded. The observation table is as follows,
https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEgijmjfisiGnFuEPYElqRPIbLD3AacuNENRGWWi2nc0EBKEaTQZtqTBC1tf5YHeNGPgFTWiJH3WkMFc7OqI97p5NcxlPdHhzhaHZHnNVaTjp81w1c6dio_lIaeWG_HJm4qYp52RmnPgwgY/s1600/ABB14.jpeg

       Now the current flowing through the windings are rated current hence the total copper loss is full load copper loss. Now the voltage supplied is low which is a small fraction of the rated voltage. The iron losses are function of applied voltage. So the iron losses in reduced voltage test are very small. Hence the wattmeter reading is the power loss which is equal to full load copper losses as iron losses are very low.
...           Wsc = (Pcu) F.L. = Full load copper loss
      Calculations : From S.C. test readings we can write,
              Wsc = Vsc Isc cos Φsc
...            cos Φsc = Vsc Isc /Wsc = short circuit power factor
               Wsc = Isc2 R1e = copper loss
...             R1e =Wsc /Isc2
while        Z1e =Vsc /Isc = √(R1e2 + X1e2)
...             X1e = √(Z1e2 - R1e2)
       Thus we get the equivalent circuit parameters R1e, X1e and Z1e. Knowing the transformation ratio K, the equivalent circuit parameters referred to secondary also can be obtained.
Important Note : If the transformer is step up transformer, its primary is L.V. while secondary is H.V. winding. In S.C. test, supply is given to H.V. winding and L.V is shorted. In such case we connect meters on H.V. side which is transformer secondary through for S.C. test purpose H.V side acts as primary. In such case the parameters calculated from S.C. test readings are referred to secondary which are R2e, Z2e and X2e. So before doing calculations it is necessary to find out where the readings are recorded on transformer primary or secondary and accordingly the parameters are to be determined. In step down transformer, primary is high voltage itself to which supply is given in S.C. test. So in such case test results give us parameters referred to primary i.e. R1e, Z1e and X1e.
Key point : In short, if meters are connected to primary of transformer in S.C. test, calculations give us R1e and Z1e if meters are connected to secondary of transformer in S.C. test calculations give us R2e and Z2e.

3. Calculation of Efficiency from O.C. and S.C. Tests
      We know that,
       From O.C. test, Wo =  Pi
       From S.C. test,  Wsc = (Pcu) F.L.
https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEjMvxo7N1luJlhonU9lfvjB0msLTgxI3WCxDFPYDFcwJdf1d-wfWAbKqNYDtnqzI4mKpDaXiIzX614eAje9l39J1xjUjQjRzOmfShQ5RST3FGJqGUutovlaTbYUVBX-fDgKfSkrRexn-Ec/s1600/ABB15.jpeg

Thus for any p.f. cos Φ2 the efficiency can be predetermined. Similarly at any load which is fraction of full load then also efficiency can be predetermined as,
https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEhunQLbGDsvjEjuvhkr-c4K-CXX5fDgOacn8Wd6r3TF36mmmcTR_iRUWcrvYFbPjptUByTDFo5_bMHUtt1yn9hFhopkGNjJatqGUSbByH0LZKBdJAjAuC-7RaTY4TDrKMXlHSJkIrIZwA8/s1600/ABB16.jpeg

where       n = fraction of full load
where       I2= n (I2) F.L.

4 Calculation of Regulation
       From S.C. test we get the equivalent circuit parameters referred to primary or secondary.
       The rated voltages V1, V2 and rated currents (I1) F.L. and (I2) F.L. are known for the given transformer. Hence the regulation can be determined as,
https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEjQorSd6kXblhrbPKF8na6htv3zLFM8iw4s6wLuelgti-M-GJA6wR-WPOssF86ZkZU4lX2N012OS-eA8ZwXXhIm2IFXV_Uqo4cFbDKpcdemUdrIQO8l-ovpQeD8x0DMm9vDRDPgd7vRsCM/s1600/ABB18.jpeg

       where I1, I2 are rated currents for full load regulation.
       For any other load the currents I1, I2 must be changed by fraction n.
...    I1, I2 at any other load = n (I1) F.L., n (I2) F.L.
Key Point : Thus regulation at any load and any power factor can be predetermined, without actually loading the transformer.


For Procedure and Circuit Diagram, See your Electrical Laboratory Manual on page 3. 

 Fill Up Tables in Your Manual and Continue To….

PRECAUTIONS:

For Precautions, See General Electrical Lab Precautions

Answers to Questions:
No Questions in this experiment.

Please Do Not Use This Reference Material WORD FOR WORD View Terms Of usage policy Page of this site for more Info on how to use this site









Share on Google Plus

About Stephen Djes

Stephen Djes is a passionate Graduate of Engineering from the University of Benin, and he is geared towards helping fellow engineering students in the great institution of UNIBEN to do better at academics.
    Blogger Comment
    Facebook Comment