EE206 - The Single Phase Transformer

EE206
Please Do Not Use This Reference Material WORD FOR WORD View Terms Of usage policy Page of this site for more Info on how to use this site

Title: The Single Phase Transformer
Aim: To verify that the voltage ratio between the primary voltage and secondary voltage of a transformer is equal in turns with the winding ratio, and to study the characteristics of a transformer on No-Load and on Load
Apparatus:
(See Apparatus in your Lab Manual on page 25)

Please Do Not Use This Reference Material WORD FOR WORD View Terms Of usage policy Page of this site for more Info on how to use this site

THEORY:
The single-phase transformer is used, above all, in mains power units for supplying different types of electrical equipment. The transformer is then used to change the mains voltage to other voltages that are required in the equipment.
The single-phase transformer consists of two windings on a common iron core. If one of the windings is connected to an AC voltage V1, an alternating magnetic field will be set up in the iron core. This field will then induce an AC voltage V2 in the other winding.
The ratio between these voltages is the same as the ratio between the number of turns on the two windings:

V1/V2=N1/N2

The winding for the higher voltage is called the up winding and the other winding is called the down winding.
If the transformer is connected in an electric circuit the input winding is called the primary winding.
The other winding, which gives out power, is called the secondary winding.
In reality the up and down windings of a transformer are wound on top of each other, and not side by side as shown in the figure. This arrangement results in reduced leakage magnetic flux, and thus a smaller voltage drop in the transformer on load. In transformer MV 1911, however, the windings are laid side by side so that a larger, and hence easier to measure, voltage drop is obtained in the transformer when carrying out the laboratory exercises.

Transformer on No-Load
Let us consider one electrical transformer with only core losses, which means, it has only core losses but no copper loss and no leakage reactance of transformer. When an alternating source is applied in the primary, the source will supply the current for magnetizing the core of transformer. But this current is not the actual magnetizing current, it is little bit greater than actual magnetizing current.

Actually, total current supplied from the source has two components, one is magnetizing current which is merely utilized for magnetizing the core and other component of the source current is consumed for compensating the core losses in transformer. Because of this core loss component, the source current in transformer on no-load condition supplied from the source as source current is not exactly at 90° lags of supply voltage, but it lags behind an angle θ is less than 90°. If total current supplied from source is Io, it will have one component in phase with supply voltage V1 and this component of the current Iw is core loss component. This component is taken in phase with source voltage, because it is associated with active or working losses in transformer. Other component of the source current is denoted as Iμ.

This component produces the alternating magnetic flux in the core, so it is watt-less; means it is reactive part of the transformer source current.
Hence Iμ will be in quadrature with V1 and in phase with alternating flux Φ.
Hence, total primary current in transformer on no-load condition can be represented as
Now you have seen how simple is to explain the theory of transformer in no-load.

Transformer On-Load
Theory of Transformer On Load But Having No Winding Resistance and Leakage Reactance

Now we will examine the behavior of above said transformer on load, that means load is connected to the secondary terminals. Consider, transformer having core loss but no copper loss and leakage reactance. Whenever load is connected to the secondary winding, load current will start to flow through the load as well as secondary winding.

This load current solely depends upon the characteristics of the load and also upon secondary voltage of the transformer. This current is called secondary current or load current, here it is denoted as I2. As I2 is flowing through the secondary, a self mmf in secondary winding will be produced. Here it is N2I2, where, N2 is the number of turns of the secondary winding of transformer.
This mmf or magneto motive force in the secondary winding produces flux φ2. This φ2 will oppose the main magnetizing flux and momentarily weakens the main flux and tries to reduce primary self induced emf E1. If E1 falls down below the primary source voltage V1, there will be an extra current flowing from source to primary winding. This extra primary current I2′ produces extra flux φ′ in the core which will neutralize the secondary counter flux φ2. Hence the main magnetizing flux of core, Φ remains unchanged irrespective of load.

So total current, this transformer draws from source can be divided into two components, first one is utilized for magnetizing the core and compensating the core loss i.e. Io. It is no-load component of the primary current. Second one is utilized for compensating the counter flux of the secondary winding. It is known as load component of the primary current.
Hence total no load primary current I1 of a electrical power transformer having no winding resistance and leakage reactance can be represented as follows

Where θ2 is the angle between Secondary Voltage and Secondary Current of transformer.

Now we will proceed one further step toward more practical aspect of a transformer.

Theory of Transformer On Load, With Resistive Winding, But No Leakage Reactances

Now, consider the winding resistance of transformer but no leakage reactance. So far we have discussed about the transformer which has ideal windings, means winding with no resistance and leakage reactance, but now we will consider one transformer which has internal resistance in the winding but no leakage reactance. As the windings are resistive, there would be a voltage drop in the windings.

We have proved earlier that, total primary current from the source on load is I1. The voltage drop in the primary winding with resistance, R1 is R1I1. Obviously, induced emf across primary winding E1, is not exactly equal to source voltage V1. E1 is less than V1 by voltage drop I1R1.
Again in the case of secondary, the voltage induced across the secondary winding, E2 does not totally appear across the load since it also drops by an amount I2R2, where R2 is the secondary winding resistance and I2 is secondary current or load current.
Similarly, voltage equation of the secondary side of the transformer will be

Theory of Transformer On Load, With Resistance As Well As Leakage Reactance in Transformer Windings

Now we will consider the condition, when there is leakage reactance of transformer as well as winding resistance of transformer.

Let leakage reactances of primary and secondary windings of the transformer are X1 and X2 respectively.
Hence total impedance of primary and secondary winding of transformer with resistance R1 and R2 respectively, can be represented as,


We have already established the voltage equation of a transformer on load, with only resistances in the windings, where voltage drops in the windings occur only due to resistive voltage drop. But when we consider leakage reactances of transformer windings, voltage drop occurs in the winding not only because of resistance, it is because of impedance of transformer windings. Hence, actual voltage equation of a transformer can easily be determined by just replacing resistances R1 & R2 in the previously established voltage equations by Z1 and Z2.
Therefore, the voltage equations are,
Resistance drops are in the direction of current vector but, reactive drop will be perpendicular to the current vector as shown in the above vector diagram of transformer.



For Procedure, See your Electrical Laboratory Manual on pages 25, 26 and 27.   

 Fill Up Tables in Your Manual and Continue To….

PRECAUTIONS:
For Precautions, See General Electrical Lab Precautions
Answers to Questions:
1.     Copper losses result from Joule heating and so are also referred to as "I squared R losses", in reference to Joule's First Law. This states that the energy lost eachsecond, or power, increases as the square of the current through the windings and in proportion to the electrical resistance of the conductors. 

where I is the current flowing in the conductor and R the resistance of the conductor. With I in amperes and R in ohms, the calculated power loss is given in watts.
2.     Copper Losses can be determined by the product of the square of current and the resistance the copper = I2.R


Please Do Not Use This Reference Material WORD FOR WORD View Terms Of usage policy Page of this site for more Info on how to use this site



Share on Google Plus

About Uniben Engineering

Stephen Djes is a passionate Graduate of Engineering from the University of Benin, and he is geared towards helping fellow engineering students in the great institution of UNIBEN to do better at academics.
    Blogger Comment
    Facebook Comment